No violation noted during this evaluation. | 05/08/2015 | Routine |
No violation noted during this evaluation. | 11/20/2014 | Routine |
No violation noted during this evaluation. | 06/02/2014 | Routine |
- Cleaning, Frequency and Restri
- Items:
- Physical facilities/structures
- Problems:
- Not clean
- Corrections:
- Keep clean
- Comment:
- Observed dusty ceiling vent in the dry storage room. Clean to sight and touch as needed.
- General violation description:
- 6-501.12 - (A) PHYSICAL FACILITIES shall be cleaned as often as necessary to keep them clean. (B) Except for cleaning that is necessary due to a spill or other accident, cleaning shall be done during periods when the least amount of FOOD is exposed such as after closing.
- Cleaning, Frequency and Restri
- Items:
- Physical facilities/structures
- Problems:
- Not clean
- Corrections:
- Keep clean
- Comment:
- Observed dusty ceiling vent in the dry storage room. Clean to sight and touch as needed.
- General violation description:
- 6-501.12 - (A) PHYSICAL FACILITIES shall be cleaned as often as necessary to keep them clean. (B) Except for cleaning that is necessary due to a spill or other accident, cleaning shall be done during periods when the least amount of FOOD is exposed such as after closing.
|
11/26/2013 | Routine |
- Critical: Temperature Measuring Devices,
- Items:
- Thermometer(s)
- Problems:
- Not accurate
- Corrections:
- Calibrate to requirement above.
- Comment:
- Observed one of the two metal stem thermometers is inaccurate. Calibrate this thermometer to insure accurate food temperature measurements. This thermometer was removed from service until it can be calibrated. Violation corrected.
- General violation description:
- 4-203.11 - (A) FOOD TEMPERATURE MEASURING DEVICES that are scaled only in Celsius or dually scaled in Celsius and Fahrenheit shall be accurate to ±1°C in the intended range of use. (Pf) (B) FOOD TEMPERATURE MEASURING DEVICES that are scaled only in Fahrenheit shall be accurate to ±2°F in the intended range of use. (Pf)
- Critical: Temperature Measuring Devices,
- Items:
- Thermometer(s)
- Problems:
- Not accurate
- Corrections:
- Calibrate to requirement above.
- Comment:
- Observed one of the two metal stem thermometers is inaccurate. Calibrate this thermometer to insure accurate food temperature measurements. This thermometer was removed from service until it can be calibrated. Violation corrected.
- General violation description:
- 4-203.11 - (A) FOOD TEMPERATURE MEASURING DEVICES that are scaled only in Celsius or dually scaled in Celsius and Fahrenheit shall be accurate to ±1°C in the intended range of use. (Pf) (B) FOOD TEMPERATURE MEASURING DEVICES that are scaled only in Fahrenheit shall be accurate to ±2°F in the intended range of use. (Pf)
- Cleaning Ventilation Systems,
- Items:
- Ventilation system
- Problems:
- Not clean
- Corrections:
- Keep clean
- Comment:
- Observed dirty mesh filter in exhaust hood above the Blodgett oven. Clean the mesh filter to improve filtration.
- General violation description:
- 6-501.14 - (A) Intake and exhaust air ducts shall be cleaned and filters changed so they are not a source of contamination by dust, dirt, and other materials. (B) If vented to the outside, ventilation systems may not create a public health HAZARD or nuisance or unLAWful discharge.
- Cleaning Ventilation Systems,
- Items:
- Ventilation system
- Problems:
- Not clean
- Corrections:
- Keep clean
- Comment:
- Observed dirty mesh filter in exhaust hood above the Blodgett oven. Clean the mesh filter to improve filtration.
- General violation description:
- 6-501.14 - (A) Intake and exhaust air ducts shall be cleaned and filters changed so they are not a source of contamination by dust, dirt, and other materials. (B) If vented to the outside, ventilation systems may not create a public health HAZARD or nuisance or unLAWful discharge.
|
05/16/2013 | Routine |
No violation noted during this evaluation. | 11/19/2012 | Routine |
No violation noted during this evaluation. | 05/03/2012 | Routine Inspection |
- Critical: Methods-Hot Water and Chemical
- General violation description:
- 4-703.11 - After being cleaned, EQUIPMENT FOOD-CONTACT SURFACES and UTENSILS shall be SANITIZED in: (A) Hot water manual operations by immersion for at least 30 seconds and as specified under 4-501.111
- Warewashing, Sink Requirements
- Items:
- Two compartment sink, Two compartment sink
- Locations:
- 2-compartment sink(s)
- Problems:
- Not approved for use, Not approved for use
- Corrections:
- Obtain approval for use., Obtain approval for written plan to utilize alternative method.
- Comment:
- PROVIDE 3 COMPARTMENT SINK TO PROPERLY WASH, RINSE AND SANTIZE UTENSILS AND EQUIPMENT. OPERATOR IS USING A TUB FOR 3RD COMPARTMENT SINK AS A TEMPORARY SET UP. HOWEVER, THIS FACILITY DOES NOT HAVE THE PROPER EQUIPMENT TO SANITIZE EQUIPMENT AS REQUIRED UNDER THE FOOD CODE. CALL AREA SUPERVISOR WITH QUESTIONS OR FOR INFORMATION ON POSSIBLE VARIANCE APPLICATION.
- General violation description:
- 4-301.12 - (A) Except as specified in # (C) of this section, a sink with at least 3 compartments shall be provided for manually washing, rinsing, and SANITIZING EQUIPMENT and UTENSILS. (Pf) (B) Sink compartments shall be large enough to accommodate immersion of the largest EQUIPMENT and UTENSILS. If EQUIPMENT or UTENSILS are too large for the WAREWASHING sink, a WAREWASHING machine or alternative EQUIPMENT as specified in # (C) of this section shall be used. (Pf) (C) Alternative manual WAREWASHING EQUIPMENT may be used when there are special cleaning needs or constraints and its use is APPROVED. Alternative manual WAREWASHING EQUIPMENT may include: (1) High-pressure detergent sprayers
|
10/14/2011 | Routine Inspection |
No violation noted during this evaluation. | 10/25/2010 | Routine Inspection |
No violation noted during this evaluation. | 10/26/2009 | Routine Inspection |
- Critical: Backflow Prevention, Air Gap
- Items:
- Air gap
- Problems:
- Not provided
- Corrections:
- Provide.
- Comment:
- FACILITY WASHES FRESH FRUIT IN 2-COMP SINK BUT BOTH HAVE DRAIN PIPES DIRECTLY CONNECTED TO GREASE TRAP. MUST PROVIDE AIR GAP OF AT LEAST 1 INCH FOR SANITIZE SINK AND WASH FRUIT OFF IN THIS SINK ONLY.,
- General violation description:
- 5-202.13 - An air gap between the water supply inlet and the flood level rim of the PLUMBING FIXTURE, EQUIPMENT, or nonFOOD EQUIPMENT shall be at least twice the diameter of the water supply inlet and may not be less than 25 mm (1 inch).
- Good Repair and Proper Adjustm
- Items:
- Equipment components
- Problems:
- In poor repair
- Corrections:
- Repair/replace.
- Comment:
- MILK COOLER GASKETS NOT SEALING PROPERLY CAUSING ICE BUILD UP. REPAIR.
- General violation description:
- 4-501.11 - (A) EQUIPMENT shall be maintained in a state of repair and condition that meets the requirements specified under Parts 4-1 and 4-2. (B) EQUIPMENT components such as doors, seals, hinges, fasteners, and kick plates shall be kept intact, tight, and adjusted in accordance with manufacturer's specifications. (C) Cutting or piercing parts of can openers shall be kept sharp to minimize the creation of metal fragments that can contaminate FOOD when the container is opened.
- Handwashing Signage
- Items:
- Handwashing signage
- Problems:
- Not provided
- Corrections:
- Provide.
- General violation description:
- 6-301.14 - A sign or poster that notifies FOOD EMPLOYEES to wash their hands shall be provided at all HANDWASHING SINKS used by FOOD EMPLOYEES and shall be clearly visible to FOOD EMPLOYEES.
- Temperature Measuring Devices
- Items:
- Thermometer(s) refrigeration
- Problems:
- Not provided
- Corrections:
- Provide.
- General violation description:
- 4-204.112 - (A) In a mechanically refrigerated or hot FOOD storage unit, the sensor of a TEMPERATURE MEASURING DEVICE shall be located to measure the air temperature or a simulated product temperature in the warmest part of a mechanically refrigerated unit and in the coolest part of a hot FOOD storage unit. (B) Except as specified in # (C) of this section, cold or hot holding EQUIPMENT used for POTENTIALLY HAZARDOUS FOOD (TIME/TEMPERATURE CONTROL FOR SAFETY FOOD) shall be designed to include and shall be equipped with at least one integral or permanently affixed TEMPERATURE MEASURING DEVICE that is located to allow easy viewing of the device's temperature display. (C) Paragraph (B) of this section does not apply to EQUIPMENT for which the placement of a TEMPERATURE MEASURNG DEVICE is not a practical means for measuring the ambient air surrounding the FOOD because of the design, type, and use of the EQUIPMENT, such as calrod units, heat lamps, cold plates, bainmaries, steam tables, insulated FOOD transport containers, and salad bars. (D) TEMPERATURE MEASURING DEVICES shall be designed to be easily readable. (E) FOOD TEMPERATURE MEASURING DEVICES and water TEMPERATURE MEASURING DEVICES on WAREWASHING machines shall have a numerical scale, printed record, or digital readout in increments no greater than 1°C or 2°F in the intended range of use.(Pf)
- Toilet Room Receptacle, Covere
- Items:
- Covered waste receptacle(s)
- Problems:
- Not provided
- Corrections:
- Provide.
- General violation description:
- 5-501.17 - A toilet room used by females shall be provided with a covered receptacle for sanitary napkins.
- Warewashing, Sink Requirements
- Items:
- Two compartment sink
- Problems:
- Used
- Corrections:
- Provide three compartment sink.
- Comment:
- FACILITY HAS 2-COMP SINK. INSTALL 3-COMP SINK OR MAY SUBMIT VARIANCE TO USE 2-COMP.
- General violation description:
- 4-301.12 - (A) Except as specified in # (C) of this section, a sink with at least 3 compartments shall be provided for manually washing, rinsing, and SANITIZING EQUIPMENT and UTENSILS. (Pf) (B) Sink compartments shall be large enough to accommodate immersion of the largest EQUIPMENT and UTENSILS. If EQUIPMENT or UTENSILS are too large for the WAREWASHING sink, a WAREWASHING machine or alternative EQUIPMENT as specified in # (C) of this section shall be used. (Pf) (C) Alternative manual WAREWASHING EQUIPMENT may be used when there are special cleaning needs or constraints and its use is APPROVED. Alternative manual WAREWASHING EQUIPMENT may include: (1) High-pressure detergent sprayers
|
04/23/2009 | Routine Inspection |
Restaurant representatives - add corrected or new information about Webster Elementary, 32401 Pembroke, Livonia, MI 48154 »